Danfoss VLT Aqua Drive FC 202 Operating Manual page 45

0.25-30kw
Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Maintenance, Diagnostics, a...
Number
Text
1381
The option C0 did not respond when calculating
the platform version.
1382
The option C1 did not respond when calculating
the platform version.
1536
An exception in the application-oriented control is
registered. Debug information written in LCP.
1792
The DSP watchdog is active. Debugging of power
part data, motor-oriented control data not
transferred correctly.
2049
Power data restarted.
2064–2072 H081x: Option in slot x restarted.
2080–2088 H082x: Option in slot x issued a power-up wait.
2096–2104 H983x: Option in slot x issued a legal power-up
wait.
2304
Could not read any data from power EEPROM.
2305
Missing SW version from power unit.
2314
Missing power unit data from power unit.
2315
Missing SW version from power unit.
2316
Missing lo_statepage from power unit.
2324
The power card configuration is determined to be
incorrect at power-up.
2325
A power card has stopped communicating while
main power is applied.
2326
The power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations are registered as
present.
2330
Power size information between the power cards
does not match.
2561
No communication from DSP to ATACD.
2562
No communication from ATACD to DSP (state
running).
2816
Stack overflow control board module.
2817
Scheduler slow tasks.
2818
Fast tasks.
2819
Parameter thread.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
2836
cfListMempool too small.
3072–5122 Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with
control board hardware.
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376–6231 Out of memory.
Table 7.4 Code Numbers for Internal Faults
MG20MD02
Operating Guide
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be in the power card,
in the gatedrive card, or the ribbon cable between the
power card and the gatedrive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short circuit connection. Check parameter 5-00 Digital I/O
Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short circuit connection. Check parameter 5-32 Term
X30/6 Digi Out (MCB 101).
For X30/7, check the load connected to X30/7 or remove
the short circuit connection. Check parameter 5-33 Term
X30/7 Digi Out (MCB 101).
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 supplies powered by the switch mode power
supply (SMPS) on the power card: 24 V, 5 V, ±18 V. When
powered with 24 V DC with the VLT
107 option, only the 24 V and 5 V supplies are monitored.
When powered with 3-phase mains voltage, all 3 supplies
are monitored.
WARNING 47, 24 V supply low
The 24 V DC supply is measured on the control card. The
external 24 V DC back-up supply may be overloaded,
otherwise contact the Danfoss supplier.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
card. Check for a defective control card. If an option card is
present, check for an overvoltage condition.
WARNING 49, Speed limit
When the speed is not within the specified range in
parameter 4-11 Motor Speed Low Limit [RPM] and
parameter 4-13 Motor Speed High Limit [RPM], the frequency
converter shows a warning. When the speed is below the
specified limit in parameter 1-86 Trip Speed Low [RPM]
(except when starting or stopping) the frequency converter
trips.
ALARM 50, AMA calibration failed
Contact the Danfoss supplier or Danfoss Service.
ALARM 51, AMA check U
The settings for motor voltage, motor current, and motor
power are wrong. Check the settings in parameters 1-20 to
1-25.
Danfoss A/S © 10/2016 All rights reserved.
®