Danfoss VLT Aqua Drive FC 202 Operating Manual page 73

0.25-30kw
Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Specifications
Enclosure
Power [kW (hp)]
A2
1.1–4.0
(1.5–5)
A3
5.5–7.5
(7.5–10)
A5
1.1–7.5
(1.5–10)
B1
11–18
(15–24)
B2
22–30
(30–40)
B3
11–18.5
(15–25)
B4
22–37
(30–50)
C1
37–55
(50–75)
C2
75–90
(100–125)
C3
45–55
(60–75)
C4
75–90
(100–125)
Table 8.21 525–600 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
1.1 (1.5)
1.5 (2)
2.2 (3)
A3
3 (4)
4 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
B2
18 (24)
22 (30)
30 (40)
37 (50)
C2
45 (60)
55 (75)
75 (100)
37 (50)
C3
45 (60)
Table 8.22 525–690 V, Enclosure Sizes A, B, and C
MG20MD02
Operating Guide
Recommended
Recommended
fuse size
maximum fuse
gG-10
gG-10 (5.5)
gG-16 (7.5)
gG-10 (0.75-5.5)
gG-16 (7.5)
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-63 (37)
gG-160 (37-45)
gG-100 (45)
aR-250 (55)
aR-160 (55)
aR-200 (75)
gG-63 (37)
gG-100 (45)
aR-160 (55)
aR-200 (75)
Recommended fuse size
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-32
gG-32
gG-40
gG-63
gG-63
gG-80
gG-100
gG-100
gG-125
Danfoss A/S © 10/2016 All rights reserved.
Recommended circuit
breaker
Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
aR-250
NZMB2-A250
gG-150
NZMB2-A200
aR-250
NZMB2-A250
Recommended
Recommended circuit
maximum fuse
breaker
Danfoss
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-25
CTI25M 10-16
gG-63
gG-63
gG-80
gG-100
gG-125
gG-160
gG-125
gG-160
Maximum trip level
[A]
25
25
25
63
100
50
100
160
250
150
250
Maximum trip
level [A]
16
16
16
16
16
16
16
71
8
8