Lenze AC Tech M3103S Installation & Operation Manual page 69

Ac mc3000 series
Table of Contents

Advertisement

FB @ MAX
76
This parameter should be set to the value of the process variable that corresponds to the
maximum transducer feedback signal (10 VDC or 20 mA) .
NOTE:
If a reverse acting feedback device is being used, FB @ MIN should be set
to the maximum process variable value, and FB @ MAX should be set to
the minimum process variable value .
P GAIN
77
This parameter setting represents the speed command output (in % of maximum speed)
that results from each 1% of error (1% of Parameter 75 - FB @ MIN or 76 - FB @ MAX,
whichever is larger) .
Example: If P GAIN is programmed for 5%, and the error (difference between setpoint
and feedback) is 10%, the speed command output of the Proportional term
is 50% (10 x 5 = 50) of maximum speed .
I GAIN
78
This parameter setting represents the ramp rate of the speed command output (in % of
maximum speed per second) that results from each 1% of error .
Example: If I GAIN is programmed for 0 .5 seconds, and the error is 5%, the rate of rise
of the speed command output of the Integral term is 2 .5% (0 .5 x 5 = 2 .5) of
maximum speed per second .
D GAIN
79
This parameter setting represents the speed command output (in % of maximum speed)
that results from each 1% per second change in the error .
Example: If D GAIN is programmed for 5 seconds, and the error is increasing at 2%
per second, the speed command output of the Differential term is 10% (5 x
2 = 10) of maximum speed .
NOTE:
Differential gain is used as a "shock-absorber" to dampen overshoots in fast-
acting systems . However, it can be very sensitive to "noise" on the feedback
signal and to digitizing errors, so it must be used with caution .
PID ACC
80
This parameter sets the acceleration and deceleration rate of the setpoint reference into
the PID unit . When the setpoint changes, this function will "filter" the input to the PID unit
by ramping the setpoint reference from the previous value to the new value . This will
help prevent overshoots that can occur when the PID control attempts to respond to step
changes in setpoint, resulting in smoother operation . If PID ACC is set to 0 .0 seconds,
it is effectively disabled .
MIN ALRM
81
This parameter setting represents the value that the feedback signal (in PID mode) or
speed reference signal (in open-loop speed mode) must fall below to activate the MIN/
MAX ALARM output (refer to Parameters 52, 53, and 54) .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(MAXIMUM FEEDBACk VALUE)
(PROPORTIONAL GAIN)
(INTEGRAL GAIN)
(DIFFERENTIAL GAIN)
(PID ACCEL/DECEL)
(PID MINIMUM ALARM)
M301L
65