This parameter sets the carrier frequency, or switching frequency of the output IGBT's .
Higher switching rates result in less audible noise to be emitted from the motor, but
the efficiency of the drive decreases as the carrier frequency increases . Therefore,
this parameter should be set to the lowest value which yields acceptable sound levels .
Available settings are: 2 .5 kHz, 6 kHz, 8 kHz, 10 kHz, 12 kHz and 14 kHz .
NOTE 1:
The 2 .5 kHz carrier frequency setting is a variable carrier . The carrier
frequency remains fixed at 1 .5 kHz up to 25 Hz output frequency . Above 25
Hz, the carrier is a fixed multiple of 60 times the drive's output frequency .
For example, if the output frequency of the drive was set to 45 Hz, the carrier
frequency would be 2 .7 kHz (45 Hz x 60 = 2700 Hz) . The other settings are
constant carriers that remain fixed for the entire speed range .
NOTE 2:
The ability to operate a drive at higher carrier frequencies is dependent on
the drive horsepower rating, driven load, drive enclosure, and the ambient
temperature . Operation above 8kHz requires derating the drive by multiplying
the output current rating by the following factors: 0 .94 at 10 kHz, 0 .89 at 12
kHz, and 0 .83 at 14 kHz .
START
25
WARNING!
Automatic start of equipment may result in damage to equipment
and/or injury to personnel! Automatic start should only be used on
equipment that is inaccessible to personnel .
This parameter selects the starting method for the drive, possible settings are:
NORMAL
POWER UP
AUTO 1
AUTO 2
AUTO 3
The AUTO 1 - 3 settings allow the drive to start into a spinning load after a fault or upon
application of input power . As with POWER UP, the drive MUST be set up for two-wire
start/stop control and the start command MUST be present after a fault or when power
is applied for this function to operate .
52
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(CARRIER FREQUENCY)
(START MODE)
The drive will start when the appropriate contact closure is made
on the terminal strip (REMOTE mode), or by pressing the keypad
START key (LOCAL mode) . To start the drive in NORMAL mode,
a start command must be issued at least two seconds AFTER
input power is applied .
The drive will automatically start upon application of input power .
The drive MUST be set up for a two-wire start/stop circuit (refer to
Section 14 - CONTROL WIRING), and the start command MUST
be present when power is applied for this function to operate .
FLYING AUTO RESTART - LOW performance . Synchronization
in approximately 6 seconds with current levels up to 50%
of the drive rating . This setting results in a slow, smooth
synchronization .
FLYING AUTO RESTART - MEDIUM performance .
Synchronization in approximately 1 second with current
levels up to 50% of the drive rating . This setting allows faster
synchronization while retaining smoothness .
FLYING AUTO RESTART - HIGH performance . Synchronization
in approximately 1 second with current levels up to 100% of the
drive rating . This setting allows the fastest synchronization, but
sacrifices smoothness .