SOFTWARE
63
This parameter displays the software code and revision number of the control board
software . This information is useful when contacting the factory for programming or
troubleshooting assistance . This is a "view-only" parameter, and cannot be changed .
MONITOR
64
This parameter is used to enable (ON) or disable (OFF) the MONITOR MODE function .
The functionality is explained below:
ON
OFF
PROGRAM
65
WARNING!
EXTERNAL FAULT (TB-13D) circuitry may be disabled if parameters
are reset to factory defaults! The drive must be reprogrammed after
a RESET in order to insure proper operation .
FAILURE TO DO SO MAY RESULT IN DAMAGE TO EQUIPMENT
AND/OR INJURY TO PERSONNEL!
This parameter is used to reset the programmable parameters back to the factory default
settings . This parameter has three possible settings:
MAINTAIN
RESET 60
RESET 50
NOTE 1:
This parameter will display RESET 60 or RESET 50 until a change is made
to one or more of the parameter settings . Once a parameter is changed, the
display will change to MAINTAIN .
NOTE 2:
When a reset is performed, TB-13D will default to a normally open
EXTERNAL FAULT contact because Parameter 50 - TB13D will be reset
to EXT FAULT .
HISTORY
66
This parameter is used to clear the previous faults in the FAULT HISTORY . When set
to CLEAR and the ENTER key is pushed, the display will change to MAINTAIN, and the
FAULT HISTORY will display NO FAULT for each of the eight fault histories .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(SOFTWARE VERSION)
(MONITOR)
Pressing the PROG/RUN key will activate the PASSWORD
prompt . If the ENTER key is pressed while the password value
reads 0000, the MONITOR MODE is entered and parameters
can be viewed (except for PASSWORD), but not changed .
Pressing the PROG/RUN key will activate the PASSWORD
prompt . If the ENTER key is pressed while the password value
reads 0000, it will be treated as in incorrect password and the
display will flash ERROR: INCORRECT, and then return to the
PASSWORD prompt to allow another attempt at entering the
correct password .
(PROGRAM FACTORY DEFAULTS)
Maintain parameter settings as they are .
Resets parameters to factory defaults for 60 Hz base frequency .
Resets parameters to factory defaults for 50 Hz base frequency .
(CLEAR FAULT HISTORY)
M301L
63