VOLTAGE SELECTION
9 .1
INPUT VOLTAGE RATINGS
M3100 Series drives are rated for 240/120 Vac, 50-60 Hz input . The drive will function with
input voltage of 120 Vac (+10%, -15%) at 48 to 62 Hz when wired for 120 Vac input, or
with input voltage of 240 Vac (+10%, -15%), at 48 to 62 Hz, when wired for 240 Vac input .
M3200 Series drives are rated for 240/200 Vac, 50-60 Hz input . The drive will function
with input voltages of 200 to 240 Vac (+10%, -15%), at 48 to 62 Hz .
M3400 Series drives are rated for 480/400 Vac, 50-60 Hz input . The drive will function
with input voltages of 400 to 480 Vac (+10%, -15%), at 48 to 62 Hz .
M3500 Series drives are rated for 590/480 Vac, 50-60 Hz input . The drive will function
with input voltages of 480 to 590 Vac (+10%, -15%), at 48 to 62 Hz .
To select the proper input voltage on 240/200 VAC 30-60 Hp models, 400/480 VAC 75-
150 Hp and 480/590 VAC 75-150 Hp models the PL2 plug must be in the correct position .
PL2 is located either at the lower right corner, or upper right corner of the power board,
depending on horsepower . The PL2 plug is used to select the correct input voltage . Plug
PL2 into the top and middle pins to select 240, 480, or 590 VAC or the middle and bottom
pins to select 200, 400, or 480 .
NOTE:
In addition to the voltage plug selection, Parameter 0 – LINE VOLTS must also
be programmed for the proper voltage . Refer to Section 18 - DESCRIPTION OF
PARAMETERS .
MODEL
CODE
1200
1400
1500
240 / 480 / 590 Vac INPUT
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Voltage Selection Plug (PL2)
PL2
240V
200V
400V
480V
590V
480V
PL2
MODEL
CODE
1200
200V
1400
400V
480V
1500
200 / 400 / 480 Vac INPUT
M301L
240V
480V
590V