@ TB10B
45
This parameter scales the analog output signal at TB-10B . This setting is the load (in %)
that is indicated when the TB-10B output measures 10 VDC .
Example: The drive is part of a control system that requires a 0-10 VDC signal to
indicate 0-150% drive load . If this parameter is set to 150%, the drive will
output 10 VDC at 150% load (and about 6 .7 VDC at 100% load) .
NOTE:
The output signal at TB-10B is affected by the setting of Parameter 34 - LOAD
MLT .
TB13A
47
This parameter is used to select the function of terminal TB-13A . Closing TB-13A to TB-2
activates the TB - 13A input function . The following functions can be selected:
NONE
0-10VDC
4-20 MA
SPEED#1
LOC SEL
DEC FREQ
TB13B
48
This parameter is used to select the function of terminal TB-13B . Closing TB-13B to TB-2
activates the TB - 13B function . The following functions can be selected:
NONE
0-10VDC
4-20 MA
SPEED#2
INC FREQ
58
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(TERMINAL TB-10B SCALING)
(TB-13A INPUT FUNCTION)
Disables the TB-13A function .
Selects 0-10 VDC as the AUTO speed reference input (or setpoint
source in PID mode) . The 0-10 VDC signal is wired to TB-5A
and TB-2 .
Selects 4-20 mA as the AUTO speed reference input (or setpoint
source in PID mode) . The 4-20 mA signal is wired to TB-5B and
TB-2 .
Selects PRESET SPEED #1 as the AUTO speed reference .
Selects LOCAL mode when Parameter 30 - CONTROL is set to
TB STRIP . Drive is in REMOTE mode if contact closure is not
made .
Decrease frequency setpoint . Used with the MOP (motor operated
pot) function . Refer to Section 14 .2 .6 - SPEED REFERENCE
SELECTION .
(TB-13B INPUT FUNCTION)
Disables the TB-13B function .
Selects 0-10 VDC as the AUTO speed reference input (or setpoint
source in PID mode) . The 0-10 VDC signal is wired to TB-5A
and TB-2 .
Selects 4-20 mA as the AUTO speed reference input (or setpoint
source in PID mode) . The 4-20 mA signal is wired to TB-5B and
TB-2 .
Selects PRESET SPEED #2 as the AUTO speed reference .
Increase frequency setpoint . Used with MOP (motor operated
pot) function . Refer to Section 14 .2 .6 - SPEED REFERENCE
SELECTION .
M301L