15 .2
TWO-WIRE START/STOP CONTROL
Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using
one maintained contact (such as that from a PLC) for RUN and STOP commands . Close
the contact to RUN, and open the contact to STOP . Also shown is the wiring for a 0-10
VDC or 4-20 mA speed reference signal .
The TB-2 terminals are internally tied together
1 2 5A 5B 6 10A
MAINTAINED
RUN/STOP
CONTACT
NOTES:
1 . Close TB-1 to TB-2 to RUN, and open to STOP .
2 . If REVERSE direction is required, TB-13C must be set to START REVERSE
(refer to Parameter 49 - TB13C) . If REVERSE is not required, simply jumper
TB-12A to TB-2 .
3 . Program TB-13A, 13B, or 13C to select the appropriate speed reference signal
that will control the drive speed (refer to Parameters 47, 48, and 49) . When that
TB-13 terminal is closed to TB-2, the drive will respond to the selected speed
reference signal . In the diagram above, TB-13A is programmed to select either
a 0-10 VDC or 4-20 mA signal .
4 . If the contact closure is not made between TB-13A and TB-2 to select a speed
reference, the drive will default to keypad speed control .
34
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
10B 2
12A
13A 13B 13C 13D 14 15 2
FWD
REV
(see Note 2)
M301L
16 17 18
RXA TXB
0-10 VDC or 4-20 mA
SELECT (see Note 3)