Ieee 1613 Type Tests; Table 18 - Ieee 1613 Type Tests; Table 19 - Environmental Type Tests - RuggedCom RUGGEDSWITCH RSG2288 Installation Manual

9-port modular managed gigabit ethernet switch
Table of Contents

Advertisement

Type Tests

4.2 IEEE 1613 Type Tests

IEEE
IEEE Test
1613
Clause
C37.90.3
9
C37.90.2
8
C37.90.1
7
C37.90.1
7
C37.90
6
C37.90
6

Table 18 - IEEE 1613 Type Tests

Notes:
If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During
disturbance errors may occur but recovery is automatic).
If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During
disturbance no errors will occur).
4.3 IEC Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
Humidity (Damp
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2

Table 19 - Environmental Type Tests

Note:
Class 2 refers to "Measuring relays and protection equipment for which a very high
security margin is required or where the vibration levels are very high, (e.g. shipboard
application and for severe transportation conditions)."
®
RuggedCom
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric
D.C. Power ports
Strength
A.C. Power ports
Description
Cold
Test Ad
Temperature
Dry Heat
Test Bd
Test Db
Heat, Cyclic)
Vibration
Shock
42
RuggedSwitch
+/- 4kV @ 2.5kHz
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6
cycles
2g @ (10-150) Hz
30g @ 11 ms
®
RSG2288 Installation Guide rev106
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV
+/- 4kV
+/- 4kV
5 kV
5 kV
2kVAC
1.5kVDC
2kVAC
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2

Advertisement

Table of Contents
loading

Table of Contents