Type Tests
4.2 IEEE 1613 Type Tests
Test
IEEE C37.90.3
IEEE C37.90.2
Radiated RFI
IEEE C37.90.1
Fast Transient
IEEE C37.90.1
Oscillatory
IEEE C37.90
H.V. Impulse
Dielectric
IEEE C37.90
Strength
Table 11 - IEEE 1613 Type Tests
NOTE:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur
but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will
occur).
4.3 IEC Environmental Type Tests
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Humidity (Damp Heat,
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Table 12 - Environmental Type Tests
RuggedCom
®
Description
Enclosure Contact
ESD
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Description
Test Ad
Dry Heat
Test Bd
Test Db
Cyclic)
Vibration
Tests Fc
Shock
Tests Ea
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
2kVac (Failsafe Relay)
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55 deg C, 6 cycles
2g @ (10-150) Hz
30g @ 11ms
25
RuggedSwitch
RS940G Installation Guide rev101
®
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
5 kV
5 kV
2kVac
2kVac
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2
Need help?