Ieee 1613 Type Tests; Iec Environmental Type Tests; Rs900G Ieee 1613 Type Tests - RuggedCom RUGGEDSWITCH RS900G Hardware Installation Manual

Hide thumbs Also See for RUGGEDSWITCH RS900G:
Table of Contents

Advertisement

3. Specifications

3.7.2. IEEE 1613 Type Tests

IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90.1
C37.90
C37.90
Table 3.8. RS900G IEEE 1613 Type Tests
• If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During
disturbance errors may occur but recovery is automatic).
• If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During
disturbance no errors will occur).

3.7.3. IEC Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
Table 3.9. IEC Environmental Type Tests
RuggedCom® RuggedSwitch™
IEEE 1613 Clause
9
8
7
7
6
6
Description
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
Vibration
Shock
Description
ESD
Radiated RFI
Fast Transient
Oscillatory
H.V. Impulse
Dielectric Strength
Test Levels
Test Ad
-40°C, 16 Hours
Test Bd
+85°C, 16 Hours
95% (non-condensing),
Test Db
55°C, 6 cycles
2g @ (10-150) Hz
30g @ 11 ms
20
RS900G Installation Guide Rev 107
Test Levels
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
@ 2.5kHz
D.C. Power ports
A.C. Power ports
Earth ground ports
common
Signal ports
mode @
common &
D.C. Power ports
differential
mode @
common &
A.C. Power ports
differential
mode @
5 kV (Failsafe
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
AC(Failsafe
D.C. Power ports
1.5kV DC
A.C. Power ports
Severity Levels
N/A
N/A
N/A
Class 2
Class 2
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV
1MHz
2.5kV
1MHz
2.5kV
1MHz
Relay)
5 kV
5 kV
2kV
Relay)
2kV AC

Advertisement

Table of Contents
loading

Table of Contents