RS900 Family Installation Guide

7.2 IEEE 1613 Type Tests

IEEE
IEEE
1613
Test
Clause
C37.90.
9
3
C37.90.
8
2
C37.90.
7
1
C37.90.
7
1
C37.90
6
C37.90
6

Table 26 - IEEE 1613 Type Tests

NOTE:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During
disturbance errors may occur but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During
disturbance no errors will occur).

7.3 IEC Environmental Type Tests

Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Dry Heat
IEC 60068-2-
Humidity (Damp
30
Heat, Cyclic)
IEC 60255-21-
1
IEC 60255-21-
2

Table 27 - Environmental Type Tests

 2010 RuggedCom Inc.
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
Oscillatory
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Signal ports
Dielectric
D.C. Power ports
Strength
A.C. Power ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
43
Test Levels
+/- 4kV @ 2.5kHz
2.5kV common mode @ 1MHz
2.5kV common & differential mode @
2.5kV common & differential mode @
5 kV (Failsafe Relay)
2kV AC(Failsafe Relay)
Test Levels
-40 deg. C, 16 Hours
+85 deg. C, 16 Hours
95% (non-condensing), 55°C, 6
cycles
2g @ (10-150) Hz
30g @ 11 ms
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV
+/- 4kV
+/- 4kV
1MHz
1MHz
5 kV
5 kV
1.5kV DC
2kV AC
Severity
Levels
N/A
N/A
N/A
Class 2
Class 2
Rev107