2.10 ASCII Output Format
2.10.2

Most Recent (DO Channel) Status (FRelay)

2-122
mV_¯_¯_¯_¯ mV
V_¯_¯_¯_¯_ V
° C_¯_¯_¯_ °C
f
Sign (+ or -)
dddddddd
Mantissa (00000000 to 99999999; 8 digits)
For erroneous data (data status is E), the mantissa is 99999999.
If the data status is O (±over), the mantissa is 99999999 (+over) or
–99999999 (–over).
If the data status is B (burnout), the mantissa is 99999999 (+burnout) or
–99999999 (–burnout).
pp
Exponent (00 to 05)
On channels set to Log scale (/LG), pp is a two digit integer, and the sign
before pp is + or -. If the data status is E, O, or B, this value will be +99,
including the sign.
The output in response to the command "FRelay,0" is shown below.
Syntax
When no expandable I/O is connected
EA<crlf>
M00:aaa...<crlf>
M01:aaa...<crlf>
M02:aaa...<crlf>
M03:aaa...<crlf>
M04:aaa...<crlf>
M05:aaa...<crlf>
M06:aaa...<crlf>
M07:aaa...<crlf>
M08:aaa...<crlf>
M09:aaa...<crlf>
EN<crlf>
When an expandable I/O or sub unit is connected
Only the information of detected units will be output.
EA<crlf>
Unit:nnf
M00:aaa...<crlf>
M01:aaa...<crlf>
M02:aaa...<crlf>
M03:aaa...<crlf>
M04:aaa...<crlf>
M05:aaa...<crlf>
M06:aaa...<crlf>
M07:aaa...<crlf>
M08:aaa...<crlf>
M09:aaa...<crlf>
Unit:nnf
M00:aaa...<crlf>
M01:aaa...<crlf>
M02:aaa...<crlf>
M03:aaa...<crlf>
M04:aaa...<crlf>
M05:aaa...<crlf>
M06:aaa...<crlf>
M07:aaa...<crlf>
M08:aaa...<crlf>
M09:aaa...<crlf>
:
Unit:nnf
M00:aaa...<crlf>
M01:aaa...<crlf>
M02:aaa...<crlf>
IM 04L51B01-17EN