2.10.31 Outputs the Most Recent Control Data (FCtrlData)

IM 04L51B01-17EN
The output in response to the command "FCtrlData" is shown below. Outputs the most
recent control data per loop.
Syntax
EA<crlf>
DATE_yy/mo/dd<crlf>
TIME_hh:mm:ss.mmmt<crlf>
llll,S_fddddddddE-pp,S_fddddddddE-pp,S_fddddddddE-pp,aaaa1aaaa2aaaa3aaaa4<crlf>
EN<crlf>
yy/mo/dd
Data time (year, month, day)
yy
mo
dd
hh:mm:ss.mmmt Data time (hour, minute, second, millisecond)
hh
mm
ss
mmm
A period is inserted between the minute and millisecond.
t
Reserved (space)
llll
Loop number
s
Data status
N
S
O
E
B
F
M
f
Sign (+ or -)
dddddddd
Mantissa (00000000 to 99999999; 8 digits)
If the data status is O (±over) or B (burnout), the mantissa will be the value
of -5% to 105% of the range.
If the data status is E, the mantissa is 99999999.
pp
Exponent (00 to 04)
aaaa1aaaa2aaaa3aaaa4 Alarm Status
aaaa1
aaaa2
aaaa3
aaaa4
aaaa1, aaaa2, aaaa3, or aaaa4 is set to one of the following:
PVH
PVL
SPH
SPL
DVH
DVL
DVO
DVI
OTH
OTL
PVR
If an alarm has not occurred, the alarm status is set to space.
s_fddddddddE-pp is in order of PV, SP, and OUT.
The data time outputted is not the time of a control period but the data acquisition time by a
communication command.
2.10 ASCII Output Format
Year (00 to 99)
Month (01 to 12)
Day (01 to 31)
Hour (00 to 23)
Minute (00 to 59)
Second (00 to 59)
Millisecond (000 to 999)
Normal
Skip
Over
Errors
Burnout
No data
Luck of data/Module not installed
Alarm status 1
Alarm status 2
Alarm status 3
Alarm status 4
PV high limit
PV low limit
SP high limit
SP low limit
Deviation high limit
Deviation low limit
Deviation H/L limits
Deviation within H/L limits
Control output high limit
Control output low limit
PV velocity
1
2
App
2-163