Alarm Summary (Flog) - YOKOGAWA GX10 User Manual

Gx series; gp series; gm series; smartdac+ communication command
Hide thumbs Also See for GX10:
Table of Contents

Advertisement

2.10 ASCII Output Format
2.10.9

Alarm Summary (FLog)

2-134
The output in response to the command "FLog,ALARM" is shown below.
Syntax
EA<crlf>
yyyy/mo/dd_hh:mm:ss.ttt_kkk_cccc_lss<crlf>
...
EN<crlf>
yyyy/mo/dd_hh:mm:ss.ttt Time of alarm occurrence
kkk
cccc
l
ss
If the cause of alarm is "all channel alarm ACK" or "all channel alarm OFF," the channel
number, alarm level, and alarm type will be blank.
If the cause of alarm is "individual alarm ACK," the alarm type will be blank.
Year (1900 to 2099)
yyyy
Month (01 to 12)
mo
Day (01 to 31)
dd
hh
Hour (00 to 23)
mm
Minute (00 to 59)
ss
Second (00 to 59)
ttt
Millisecond (000 to 999)
A period is inserted between the minute and
millisecond.
Alarm cause
Alarm release
OFF
ON_
Alarm occurrence
ACK
All channel alarm ACK, Individual alarm
ACK
ALL
All channel alarm OFF
Channel number (set to four spaces if the alarm cause is
"ACK" or "ALL")
Alarm level (1 to 4)
Alarm type
H_
High limit alarm
h_
Difference high limit alarm
L_
Low limit alarm
Difference low limit alarm
l_
High limit on rate-of-change alarm
R_
Low limit on rate-of-change alarm
r_
Delay high limit alarm
T_
t_
Delay low limit alarm
IM 04L51B01-17EN