Metering CT Considerations

The Envoy-S uses readings from CTs to report measurement data for PV energy production and energy
consumed by the home or business. When current transformers (CTs) are wrapped around a live wire,
the current going through the wire induces a current on the CTs primary internal winding, which in turn
induces a current on the CTs secondary internal winding. The current on the secondary winding is
proportional to the current on the original circuit and this is used for making measurements. Install the
CTs as shown in the wiring instruction for your region.
Production CTs measure power production through a connection to the solar supply main
switch.
Consumption CTs measure energy consumption through a connection to the AC mains.
To install the CTs, use a protected route in conduit for the CT wires to the Envoy-S. Install one split-core
CT per monitored phase for production metering and one split-core CT per monitored phase for
consumption metering. If you need to extend the CT leads (up to 148 meters), see "Extend CT Leads, If
Needed" on page 16.

Required Items

If you hard-wire the Envoy-S outdoors, you must install it in an IP54-rated (or better) enclosure with
conduit attachment. Note that Metallic enclosures may impair Wi-Fi signal strength. Use an
appropriately rated enclosure if hard-wiring indoors. Do not drill holes for conduit at the top of the
enclosure or anywhere that allows moisture ingress.
The Envoy-S Metered Multiphase includes a production CT and a consumption CT. You must order
additional CTs (CT-100-SPLIT) for multiphase installations. Make sure you have one CT for each phase
monitored, for both production and consumption.

Optional Items

Make sure you have the following optional items, if needed:
Enphase Mobile Connect modem (order Enphase CELLMODEM-02)
Ethernet over power line communication (PLC) bridge with Ethernet cables [order EPLC-02 (EU),
EPLC-03 (UK) or EPLC-04 (AU/NZ) separately]
Ethernet cable (use 802.3, unshielded Cat5E or Cat6). Do not use shielded twisted pair (STP)
cable.

System Metering

The Envoy-S monitors up to 600 Enphase Microinverters and up to 39 Enphase AC Batteries.
Envoy-S name and model
numbers (SKU)
Envoy-S Metered,
multiphase (ENV-S-WM-
230)
NOTE: To install multiple Envoys at a single site, see our technical brief on commercial
design at enphase.com/support.
9
Envoy-S Metered Multiphase Installation and Operation
Case
Metering / reporting
colour
Black
Integrated PV production and
home consumption metering
(accuracy +/- 1%)
© 2016 Enphase Energy Inc.
Includes AC power
cord or CTs
ready
Two split-core CTs
(CT-100-SPLIT).
Order additional CTs
to monitor multiple
phases.
141-00035 Rev 01
DRM
Yes