Conditions of Acceptability

Adhere to the installation conditions specified in this guide to take full advantage of the
finless design of this drive.
Installation Environment
The drive must be installed a control panel with a proper heat sink. The drive ambient
temperature shall not exceed 50 ºC (122 ºF) for the drives installed location.
Heatsink Plate Temperature
The aluminum panel on the back of the drive is referred to as the "heatsink plate." The
heatsink plate temperature should never exceed the following values:
CIMR-V BA
CIMR-V 2A0030~0069, CIMR-V 4A0018~0038: 80 °C
Table 6
and
Table 7
Use parameter U4-08 to check the temperature of the heatsink plate as described below.
NOTICE: The drive may be damaged if the temperature of the heatsink plate exceeds specified tolerance
levels (90 °C or 80 °C, depending on the model). Excessive heat can also shorten the performance life of
various drive components.
Checking and Monitoring Heatsink Plate Temperature
Checking Heatsink Plate Temperature Using the LED Operator
Scroll to parameter U4-08 (heatsink plate temperature).
When the temperature of the heatsink plate is 89 ºC, U4-08 will display:
Note: Parameter U4-08 is available in drive software version 1011 or later.
Checking Heatsink Plate Temperature Using an Analog Output
Example: When using Multi-Function Analog Output Terminal AM, set the parameters
shown in
Table
1.
No.
H4-01
Analog Output Terminal AM Function Selection
H4-02
Analog Output Terminal AM Gain
H4-03
Analog Output Terminal AM Bias
YASKAWA ELECTRIC TOBP C710606 21D YASKAWA AC Drive - V1000 Finless Installation Guide
, CIMR-V 2A0001~0020, CIMR-V 4A0001~0011: 90 °C
lists the thermal characteristics of the drive.
Table 1 Using Analog Output 1
Name
3 Conditions of Acceptability
Description
00408
(heatsink plate temperature)
100.0%