Cable And Fuse Sizes, 380-500 V Units - Vacon nxp/c User Manual

Table of Contents

Advertisement

CABLING AND CONNECTIONS
6.2.6

Cable and fuse sizes, 380-500 V units

The table below shows typical cable sizes and types that can be used with the converter. The final
selection should be made according to local regulations, cable installation conditions and cable
specification.
6.2.6.1
6-pulse drives
Table 13. Cable and fuse sizes for Vacon NX_5, 6-pulse supply
I
L
Frame
Type
[A]
NXC0261 5
261
FR9
NXC0300 5
300
NXC0385 5
385
FR10
NXC0460 5
460
NXC0520 5
520
NXC0590 5
590
FR11
NXC0650 5
650
NXC0730 5
730
NXC0820 5
820
FR12
NXC0920 5
920
NXC1030 5
1030
NXC1150 5
1150
FR13
NXC1300 5
1300
NXC1450 5
1450
NXC1770 5
1770
FR14
NXC2150 5
2150
1)
Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each
other. Ambient temperature is 30 °C (86 °F). EN60204-1 and IEC 60364-5-523.
2)
Odd number of supply cables possible on request. Please contact factory for more information.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Bussmann/Ferraz
Fuse I
Shawmut fuse type
170M5813 (3 pcs)
NH2UD69V500PV (3 pcs)
170M5813 (3 pcs)
NH2UD69V500PV (3 pcs)
170M5813 (3 pcs)
NH2UD69V700PV (3 pcs)
170M8547 (3 pcs)
NH3UD69V1000PV (3 pcs)
170M8547 (3 pcs)
NH3UD69V1000PV (3 pcs)
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
No additional drive fuses needed
No additional drive fuses needed
No additional drive fuses needed
No additional drive fuses needed
No additional drive fuses needed
Mains and motor
n
1)
2
[A]
cable
[mm
Cu: 3*185+95 or
700/500
2*(3*120+70)
700/500
Cu: 2*(3*120+70)
Cu: 2*(3*120+70)
700
Al: 2*(3*185Al+57Cu)
1250/
Cu: 2*(3*150+70)
1000
Al: 2*(3*240Al+72Cu)
1250/
Cu: 2*(3*185+95)
1000
Al: 2*(3*300Al+88Cu)
Cu: 2*(3*240+120)
700
Al: 4*(3*120Al+41Cu)
Cu: 4*(3*95+50)
700
Al: 4*(3*150Al+41Cu)
Cu: 4*(3*120+70)
700
Al: 4*(3*185Al+57Cu)
1250/
Cu: 4*(3*150+70)
1000
Al: 4*(3*185Al+57Cu)
1250/
Cu: 4*(3*150+70)
1000
Al: 4*(3*240Al+72Cu)
1250/
Cu: 4*(3*185+95)
1000
Al: 4*(3*300Al+88Cu)
Cu:5*(3*150+70)
Al:6*(3*185+57Cu)
Cu:5*(3*185+95)
Al:6*(3*240+72Cu)
Cu:6*(3*185+95)
Al:6*(3*240+72Cu)
Cu: 6*(3*240+120)
Al: 8*(3*240+72Cu)
Cu: 8*(3*185+95)
Al: 8*(3*300+88Cu)
vacon • 45
No. of
No. of
supply
motor
]
cables
cables
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
2)
Even/Odd
Even
2)
Even/Odd
Even
2)
Even/Odd
Even
Even
Even
Even
Even
Even
Even
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even
Even
Even
Even
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents