1.2 Modbus Function Code Support

HRT-710 supports the following Modbus Function Code commands.
[ Table 1: Modbus Function Codes ]
FC
01
Read multiple coils status
02
Read multiple input discretes
03
Read multiple Holding registers
04
Read multiple input registers
05
Write single coil
06
Write single register
15
Force multiple coils
16
Write multiple registers

1.3 Specifications

[
UART Spec. ]
COM1: RS-232(3 wire) / RS-422 / RS-485
Connector: 9-pin screwed terminal block
Baud Rate: 1200 ~ 115200 bps
Data Format:
[1] data bits : 7/8
[2] parity : None/Odd/Even
[3] stop bit : 1/2
[ HART Spec. ]
Channel number: 1
Connector: 2-pin screwed terminal block
Operates as a HART Master station and supports all HART commands
Frame: Short or Long
Network: Point to Point or Multi-drop
Max. 15 HART modules
Max. 100 user commands and 32 default commands
[ Power Requirement ]
Unregulated +10 ~ +30 V
Power reverse protection, Over-Voltage brown-out protection
Power consumption: 1 W
HRT-710 User Manual (Version 1.24, June/2015)