Figure 46: The window of through mode
It is used to send / receive HART command directly.
EX: Send a short frame HART command 0 and receive the response.
(1) In ―Send‖ field, fill in the data - ―0xFF 0xFF 0xFF 0xFF 0xFF 0x02
0x80 0x00 0x00‖ and then click ―Send‖ button to send HART Cmd.
(2) Click ―Update‖ button to show the response of HART device.
Warning: Before using through mode function, please check the
below items:
(1) The ―RUN‖ led is always on.
(2) The ―auto polling‖ function is disabled. (Refer to section 5.3.4.2 –
―The Basic Operation of System item‖)
5.3.4.8 Format Translation
Figure 47: The window of format translate
HRT-710 User Manual (Version 1.24, June/2015)