Byte 0:
Byte 1~53:
Byte 54:
Byte 55~109:
Byte 110~113:
Byte 114~115:
(10) Module status reset function:
When set the value is bigger than zero, the module will clear ―module
request count‖, ―module response count‖, ―module error count‖,
―module error status‖ and set ―module error command index‖ to 255.
(11) Auto Polling function:
When set the value to be 1, the module will execute all HART polling
commands automatically.
(12) Output Trigger function:
If change the value, the module will refer to the index value (0~99,
255 is for through mode) of trigger command to execute the
corresponding user command.
Ex: If the index of trigger command is 0 and the output trigger
function value is 1, when change the value of output trigger function
from 1 to 2, the module will execute the user command (index = 0).
(13) Default CMD(3)(S) Data: (FW_v1.5)
By using the address, users do not need to add the simple format of
User CMD(3). Just do the below setting, then
get the HART Cmd(3) data easily.
[1] Set
"Default CMD(3) mode‖ to‖Polling‖.
[2] Set
"Swap mode"
[3] Run
HRT-710 User Manual (Version 1.24, June/2015)
The length of send data (1 Byte)
The record of send data (Max. 53 Bytes)
The length of receive data (1 Byte)
The record of receive data (Max. 55 Bytes)
The time stamp record (4 Bytes)
Reserved (2 Bytes)
to
‖Save to
Device‖ function.
―W&B‖.
HMI or SCADA can
PAGE: 27