Quick Transfer Of Parameter Settings When Using Glcp; Initialization To Default Settings - Danfoss VLT HVAC Drive FC 102 Instruction Manual

315–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Operate the Adjustab...
5.3.4 Quick Transfer of Parameter Settings
when Using GLCP
Once the set-up of an adjustable frequency drive is
complete, store (backup) the parameter settings in the
GLCP or on a PC via MCT 10 Set-up Software.
WARNING
Stop the motor before performing any of these
5
5
operations.
Data storage in the LCP:
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [1] All to LCP.
4.
Press [OK].
All the parameter settings are now stored in the GLCP as
indicated by the progress bar. When 100% is reached,
press [OK].
The GLCP can now be connected to another adjustable
frequency drive, and the parameter settings can be copied
to this adjustable frequency drive.
Data transfer from the LCP to the adjustable frequency
drive
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [2] All from LCP.
4.
Press [OK].
The parameter settings stored in the GLCP are now
transferred to the adjustable frequency drive, as indicated
by the progress bar. When 100% is reached, press [OK].

5.3.5 Initialization to Default Settings

There are two ways to initialize the adjustable frequency
drive to default:
Recommended initialization
Manual initialization
Be aware that they have different impact according to the
following description.
72
®
VLT
HVAC Drive FC 102
Recommended initialization (via
parameter 14-22 Operation Mode)
1.
2.
3.
4.
5.
6.
7.
Parameter 14-22 Operation Mode initializes all except:
NOTICE!
Parameters selected in parameter 0-25 My Personal Menu
stay present with default factory setting.
Danfoss A/S © 08/2014 All rights reserved.
Select parameter 14-22 Operation Mode.
Press [OK].
Select [2] Initialization (for NLCP select "2").
Press [OK].
Remove power to unit and wait for the display to
turn off.
Reconnect power and the adjustable frequency
drive is reset. Note that first start-up takes a few
more seconds than normal.
Press [Reset].
Parameter 14-50 RFI 1.
Parameter 8-30 Protocol.
Parameter 8-31 Address.
Parameter 8-32 Baud Rate.
Parameter 8-35 Minimum Response Delay.
Parameter 8-36 Max Response Delay.
Parameter 8-37 Maximum Inter-Char Delay.
Parameter 15-00 Operating hours to
parameter 15-05 Over Volts.
Parameter 15-20 Historic Log: Event to
parameter 15-22 Historic Log: Time.
Parameter 15-30 Alarm Log: Error Code to
parameter 15-32 Alarm Log: Time.
MG11F522