315–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

General Specifications
Line Power Supply 3 x 525–690 V AC
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure protection rating IP21
Enclosure protection rating IP54
Enclosure protection rating IP00
Output current
Continuous (at 550 V) [A]
Intermittent (60 s overload) (at 550 V)
[A]
Continuous (at 575/690 V) [A]
Intermittent (60 s overload) (at 575/
690 V) [A]
7
7
Continuous KVA (at 550 V) [KVA]
Continuous KVA (at 575 V) [KVA]
Continuous KVA (at 690 V) [KVA]
Maximum input current
Continuous (at 550 V) [A]
Continuous (at 575 V) [A]
Continuous (at 690 V) [A]
Maximum cable size, line power, motor
and load share [mm
Maximum cable size, brake [mm
(AWG)]
Maximum external pre-fuses [A]
Estimated power loss
at rated maximum load [W]
Estimated power loss
at rated maximum load [W]
Weight,
enclosure protection ratings IP21, IP54
[kg (lb)]
Weight, enclosure protection rating
IP00 [kg (lb)]
Efficiency
4)
Output frequency
Heatsink overtemperature trip
Power card ambient trip
Table 7.3 Line Power Supply 3 x 525–690 V AC
120
®
VLT
P450
355
450
450
E1
E1
E2
470
517
450
495
448
448
538
453
434
434
2x240 (2x500
2
mcm)
(AWG)]
2
2x185 (2x350
mcm)
1)
700
5323
3)
, 600 V
5529
3)
, 690 V
263 (580)
221 (487.3)
110 °C (230
°F)
Danfoss A/S © 08/2014 All rights reserved.
HVAC Drive FC 102
P500
400
500
500
E1
E1
E2
523
575
500
550
498
498
598
504
482
482
4x240 (4x500 mcm)
2x185
(2x350 mcm)
700
6010
6239
263 (580)
221 (487.3)
0–525 Hz
95 °C (203 °F)
85 °C (185 °F)
P560
450
600
560
E1
E1
E2
596
656
570
627
568
568
681
574
549
549
4x240 (4x500 mcm)
4x240 (4x500 mcm)
2x185
(2x350 mcm)
(2x350 mcm)
900
7395
7653
272 (600)
236 (520.3)
0.98
110 °C (230 °F)
P630
500
650
630
E1
E1
E2
630
693
630
693
600
627
753
607
607
607
2x185
900
8209
8495
313 (690)
277 (611)