Danfoss VLT HVAC Drive FC 102 Instruction Manual page 79

315–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Program
Group
Title
20-**
FC Closed-loop
21-**
Extended Closed-loop
22-**
Application Functions
23-**
Time-based Functions
MG11F522
Instruction Manual
Function
Parameters used to configure the closed-loop PI(D) controller, which controls the speed of the
pump, fan or compressor in closed-loop mode including:
Defining where each of the three possible feedback signals come from (for example, which
analog input or the BMS HLI).
Conversion factor for each of the feedback signals. An example could be a pressure signal
used for indication of flow in an AHU or converting from pressure to temperature in a
compressor application).
Engineering unit for the reference and feedback (for example, Pa, kPa, m Wg, in Wg, bar,
m3/s, m3/h, °C, °F, etc).
The function (for example, sum, difference, average, minimum or maximum) used to calculate
the resulting feedback for single-zone applications or the control philosophy for multi-zone
applications.
Programming of the setpoints.
Manual tuning or auto-tuning of the PI(D) loop.
Parameters used to configure the three extended closed-loop PI(D) controllers. The controllers
can, for example, be used to control external servos (for example, chilled water valve to maintain
supply air temperature in a VAV system) including:
Engineering unit for the reference and feedback of each controller (for example, °C, °F).
Defining the range of the reference/setpoint for each controller.
Defining where each of the references/setpoints and feedback signals come from (for
example, which analog input or the BMS HLI).
Programming of the setpoint, and manual tuning or auto-tuning of each of the PI(D)
controllers.
Parameters used to monitor, protect and control pumps, fans and compressors, including:
No-flow detection and protection of pumps (including auto-setup of this function).
Dry-pump protection.
End-of-curve detection and protection of pumps.
Sleep mode (especially useful for cooling tower and booster pump sets).
Broken-belt detection (typically used for fan applications to detect no air flow instead of
using a ∆p switch installed across the fan).
Short-cycle protection of compressors and pump flow compensation of setpoint (especially
useful for secondary chilled water pump applications where the ∆p sensor has been installed
close to the pump and not across the furthest most significant load(s) in the system.
Using this function can compensate for the sensor installation and help to realize the
maximum energy savings).
Time-based parameters including:
Parameters used to initiate daily or weekly actions based on the built-in real time clock. The
actions could be change of setpoint for night set-back mode or start/stop of the pump/fan/
compressor start/stop of an external equipment).
Preventive maintenance functions, which can be based on running or operating hour time
intervals or on specific dates and times.
Energy log (especially useful in retrofit applications or where information of the actual
historical load (kW) on the pump/fan/compressor is of interest).
Trending (useful in retrofit or other applications where there is an interest to log operating
power, current, frequency or speed of the pump/fan/compressor for analysis and a payback
counter.
Danfoss A/S © 08/2014 All rights reserved.