How to Program
After pressing [Quick Menu], the different options in the
Quick Menu are listed. See also Figure 6.1 and Table 6.3 to
Table 6.6.
Example of using the Quick Set-up
To set the ramp-down time to 100 s, follow this procedure:
1.
Select Quick Set-up. Parameter 0-01 Language in
Quick Set-up appears.
2.
Press [
] repeatedly until parameter 3-42 Ramp 1
Ramp-down Time appears with the default setting
of 20 s.
3.
Press [OK].
4.
Press [
] to highlight the third digit before the
comma.
5.
Change 0 to 1 by pressing [
6.
Press [
] to highlight the digit 2.
7.
Change 2 to 0 by pressing [
8.
Press [OK].
The new ramp-down time is now set to 100 s.
Figure 6.1 Quick Menu View
Access the 18 most important set-up parameters of the
adjustable frequency drive via Quick Set-up. After
programming, the adjustable frequency drive is ready for
operation. The 18 Quick Set-up parameters are shown in
Table 6.2.
Parameter
Parameter 0-01 Language
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
1)
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 1-28 Motor Rotation Check
MG11F522
Instruction Manual
Parameter
Parameter 3-41 Ramp 1 Ramp-up Time
Parameter 3-42 Ramp 1 Ramp-down Time
Parameter 4-11 Motor Speed Low Limit [RPM]
Parameter 4-12 Motor Speed Low Limit [Hz]
Parameter 4-13 Motor Speed High Limit [RPM]
Parameter 4-14 Motor Speed High Limit [Hz]
Parameter 3-19 Jog Speed [RPM]
Parameter 3-11 Jog Speed [Hz]
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-40 Function Relay
1) The information shown in the display depends on the selections
made in parameter 0-02 Motor Speed Unit and
].
parameter 0-03 Regional Settings. The default settings of
parameter 0-02 Motor Speed Unit and parameter 0-03 Regional
Settings depend on which region of the world the adjustable
].
frequency drive is supplied to but can be reprogrammed as required.
2) Parameter 5-40 Function Relay is an array. Select between [0]
Relay1 or [1] Relay2. Standard setting is [0] Relay1 with the default
option [9] Alarm.
For detailed information about settings and programming,
see the VLT
NOTICE!
If [0] No Operation is selected in parameter 5-12 Terminal
27 Digital Input, no connection to +24 V on terminal 27
is necessary to enable start.
If [2] Coast Inverse (factory default value) is selected in
parameter 5-12 Terminal 27 Digital Input, a connection to
+24 V is necessary to enable start.
[Units]
[kW]
[hp]
[V]
[Hz]
[A]
[RPM]
[Hz]
Danfoss A/S © 08/2014 All rights reserved.
1)
2)
Table 6.2 Quick Set-up Parameters
®
HVAC Drive FC 102 Programming Guide.
0-01 Language
Option:
Function:
Defines display language. The adjustable
frequency drive is delivered with four
different language packages. English and
German are included in all packages.
English cannot be erased or manipulated.
[0]
English
Part of language packages 1–4
*
[1]
Deutsch
Part of language packages 1–4
[2]
Francais
Part of language package 1
[3]
Dansk
Part of language package 1
[4]
Spanish
Part of language package 1
[5]
Italiano
Part of language package 1
[6]
Svenska
Part of language package 1
[7]
Nederlands
Part of language package 1
[Units]
[s]
[s]
[RPM]
1)
[Hz]
[RPM]
[Hz]
1)
[RPM]
[Hz]
6
79
6