Danfoss VLT HVAC Drive FC 102 Instruction Manual page 75

315–1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Operate the Adjustab...
Manual initialization
NOTICE!
When carrying out manual initialization, serial communi-
cation, RFI filter settings and fault log settings are reset.
Manual initialization removes parameters selected in
parameter 0-25 My Personal Menu.
1.
Disconnect from the line power and wait until
the display turns off.
2.
Press
2a
[Status] - [Main Menu] - [OK] at the
same time while powering up for the
LCP 102, graphical LCP.
2b
[Menu] while powering up for LCP 101,
numerical LCP.
3.
Release the keys after 5 s.
4.
The adjustable frequency drive is now
programmed according to default settings.
This parameter initializes all except:
Parameter 15-00 Operating hours
Parameter 15-03 Power-ups
Parameter 15-04 Over Temps
Parameter 15-05 Over Volts
MG11F522
Instruction Manual
Danfoss A/S © 08/2014 All rights reserved.
5
5
73