Starting Up The Drive For The First Time; Parameter Settings; Parameter Setting Overview; Uploading And Downloading Parameter Settings - Danfoss VLT HVAC Drive FC 102 Operating Manual

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

VLT® HVAC Drive FC 102
Operating Guide
4.
Press [►] for positive speed reference (parameter 1-06 Clockwise Direction at [0] Normal).
5.
Check feedback in parameter 16-57 Feedback [RPM].
-
If feedback is positive, the test was successful.
-
If feedback is negative, the encoder connection is wrong. Use either parameter 5-71 Term 32/33 Encoder Direction or
parameter 17-60 Feedback Direction to inverse the direction, or reverse the encoder cables. Parameter 17-60 Feedback
Direction is only available with the VLT® Encoder Input MCB 102 option.

7.4 Starting Up the Drive for the First Time

The procedure in this section requires user-wiring and application programming to be completed. The following procedure is rec-
ommended after application setup is completed.
MOTOR START
Starting the drive can cause the motor to start. Failure to ensure that the motor, system, and any attached equipment are ready
for start can result in personal injury or equipment damage.
-
Ensure that equipment is safe to operate under any condition.
-
Ensure that the motor, system, and any attached equipment are ready for start.
1.
Press [Auto On].
If warnings or alarms occur, see the Warnings and Alarms section.
2.
Apply an external run command. Examples of external run commands are a switch, button, or programmable logic control-
ler (PLC).
3.
Adjust the speed reference throughout the speed range.
4.
Ensure that the system is working as intended by checking the sound and vibration levels of the motor.
5.
Remove the external run command.

7.5 Parameter Settings

7.5.1 Parameter Setting Overview

Parameters are operational settings accessed through the LCP that are used to configure and operate the drive and motor for spe-
cific applications.
Some parameters have different default settings for international or North America. For a list of the different default values, see the
International/North American Default Parameter Settings section.
Parameter settings are stored internally in the drive, allowing the following advantages:
Parameter settings can be uploaded into the LCP memory and stored as a back-up.
Multiple units can be programmed quickly by connecting the LCP to the unit and downloading the stored parameter settings.
Settings that are stored in the LCP are not changed when restoring factory default settings.
Changes made to default settings and parameter variables are stored and available for viewing in the quick menu. See the LCP
Menu section.

7.5.2 Uploading and Downloading Parameter Settings

The drive operates using parameters stored on the control card, which is located within the drive. The upload and download func-
tions move the parameters between the control card and the LCP.
Procedure
1.
Press [Off].
2.
Go to parameter 0-50 LCP Copy and press [OK].
3.
Select 1 of the following:
-
- To upload data from the control card to the LCP, select [1] All to LCP.
-
- To download data from the LCP to the control card, select [2] All from LCP.
116 | Danfoss A/S © 2021.11
W A R N I N G
Commissioning
AQ262141314214en-000301 / 130R0880