General Specifications
7.5 Electrical Data
Line Power Supply 3 x 380–480 V AC
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Enclosure protection rating IP21
Enclosure protection rating IP54
Enclosure protection rating IP00
Output current
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V)
[A]
Continuous (at 460/480 V) [A]
Intermittent (60 s overload) (at
7
7
460/480 V) [A]
Continuous KVA (at 400 V) [KVA]
Continuous KVA (at 460 V) [KVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/480 V) [A]
Maximum cable size, line power,
motor and load share [mm
Maximum cable size, brake [mm
2)
(AWG
)
Maximum external pre-fuses [A]
Estimated power loss
at rated max. load [W]
Estimated power loss
at rated maximum load [W]
Weight,
enclosure protection rating IP21, IP54
[kg (lb)]
Weight,
enclosure protection rating IP00 [kg
(lb)]
4)
Efficiency
Output frequency
Heatsink overtemperature trip
Power card ambient trip
Table 7.1 Line Power Supply 3 x 380–480 V AC
118
®
VLT
HVAC Drive FC 102
P315
315
450
E1
E1
E2
600
660
540
594
416
430
590
531
4 x 240
2
2)
(AWG
)]
(4 x 500 mcm)
2
2 x 185
(2 x 350 mcm)
1)
700
6790
3)
, 400 V
6082
3)
, 460 V
263 (580)
221 (487.3)
Danfoss A/S © 08/2014 All rights reserved.
P355
P400
355
400
500
600
E1
E1
E1
E1
E2
E2
658
745
724
820
590
678
649
746
456
516
470
540
647
733
580
667
4 x 240
4 x 240
(4 x 500 mcm)
(4 x 500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
800
900
7701
8677
6953
7819
270 (595.5)
272 (600)
234 (516)
236 (520.3)
0.98
0–590 Hz
110 °C (230 °F)
75°C (167 °F)
P450
450
600
E1
E1
E2
800
880
730
803
554
582
787
718
4 x 240
(4 x 500 mcm)
2 x 185
(2 x 350 mcm)
900
9473
8527
313 (690)
277 (611)
85 °C (185 °F)
MG11F522