Addressing
6.1 Slot-oriented address allocation for modules (default addresses for centralized I/O)
Module start addresses
The following table shows the assignment of module start addresses to slot numbers and
racks.
In the case of input/output modules, the input addresses and output addresses start from the
same module start address.
Table 6- 1
Module start addresses of signal modules
Module
Module start
carrier
addresses
0
Digital
Analog
1
Digital
Analog
The FM and CP modules are assigned to the analog address range.
1)
Note
Do not insert any non-configured modules centrally. Modules that are installed but not
configured are repeatedly addressed via the I/O bus. This requires additional computing
time.
134
1
2
PS
SIMOTION C
1)
-
-
1)
Slot number
3
4
5
IM 365 S
0
4
256
272
IM 365 R
32
36
384
400
6
7
8
9
8
12
16
20
288
304
320
336
40
44
48
52
416
432
448
464
Operating Instructions, 02/2012
10
11
24
28
352
368
56
60
480
496
SIMOTION C