Siemens SIMOTION C Operating Instructions Manual page 124

Hide thumbs Also See for SIMOTION C:
Table of Contents

Advertisement

Connecting
5.2 Networking
Example
The following figure shows an example configuration of a subnet with SIMOTION C.
Figure 5-19
Segment in subnet
The baud rate determines the cable length of a subnet segment (see the following table).
Table 5- 8
With isolated interface
1)
124
Networking example
Permitted cable lengths of a subnet segment for specific baud rates
Baud rate
9.6 to 187.5 bits/s
500 Kbits/s
1.5 Mbit/s
3 to 12 Mbits/s
Max. cable length of a segment (in m)
1000
1)
400
200
100
Operating Instructions, 02/2012