Grid Interconnection Details

Both the Enphase IQ 6 and the IQ 6+ Microinverter are grid support interactive inverters. This type of
inverter is also known as a Grid Support Utility Interactive Inverter (GSUII). The IQ 6 and IQ 6+ also
comply with California Rule 21 - 2016 and Hawaii Rule 14H - 2017.

Grid Profiles

IQ 6 and IQ 6+ Microinverters have field-adjustable voltage and frequency trip points. Trip points are input
voltage and frequency values that trigger the microinverters to shut down when the values are exceeded.
If local regulations require adjustments to these trip points, or if the grid profile was not set up during
registration, the installer can set up the system to use an alternate Grid Profile (set of trip points).
NOTE: Only an authorized installer, following the requirements of the local electrical utility, is
allowed to make Grid Profile adjustments.
NOTE: Grid profile changes are applied only after a microinverter is detected.
In some regions and in some situations, microinverter trip points may be adjusted to account for high grid
voltage or for local conditions.
Grid profile management tasks include:
Set the grid profile for your region
View or verify current trip point settings
Generate a report for confirmation of site settings to the utility or other authority
To modify the grid profile or the parameters within the grid profile, installers must log in to their Enlighten
account using their credentials.
The following tables show the parameter settings for the grid profiles available for North America:
NOTE: Simultaneous use of Fixed Power Factor and Volt/VAr is not supported.

Manufacturer's Stated Accuracy

Measurement
Volts
Amps
Watts
VAr
Displacement power factor
Hz
Time
31
Default Tolerance of Measurement
The greater of +/- 2 cycles or 0.1% of total clearing time
© 2017 Enphase Energy Inc. All rights reserved.
IQ 6 / IQ 6+ Micro Installation and Operation
+/- 1%
+/- 2%
+/- 5%
+/- 3%
+/- 2%
+/- 0.1 Hz
141-00034-01