SA10: Low/High Frequency Ride Through (L/H FRT) and Must Trip Settings

SA11: Ramp Rate (RR) and Soft Start (SS)

SA12: Specified Power Factor (SPF), aka (INV3)

SA13: Volt/VAr Mode (VV)

Reactive power absorption (inductive, under excited)
Reactive power production (capacitive, overexcited)
33
High frequency 2-time
High frequency 2-magnitude
High frequency 1-time
High frequency 1-magnitude
Low frequency 1-time
Low frequency 1-magnitude
Low frequency 2-time
Low frequency 2-magnitude
Ramp-up rate
%Irated/s
Soft start ramp rate
%Irated/s
Inductive, under excited, power factor
Capacitive, overexcited, power factor
Minimum AC EPS voltage range
Maximum EUT input voltage
© 2017 Enphase Energy Inc. All rights reserved.
IQ 6 / IQ 6+ Micro Installation and Operation
Ride Through
Units
Max
s
NA
Hz
NA
s
599.8
Hz
65
s
599.8
Hz
59.9
s
NA
Hz
NA
Adjustment Range
Units
Max
100
100
Units
VAr/W
VAr/W
Units
P.U.
P.U.
AC power
W
VAr
VAr
Slope
VAr/V
Deadband
V
Must Trip
Min
Max
NA
0.5
NA
65
0.8
600
60.1
65
0.8
600
57
59.9
NA
0.5
NA
59.9
Tolerance
Min
1
+/- 3% I rated
0.11
+/- 3% I rated
Adjustment Range
Max
Min
-0.7
-1.0
1.0
0.7
Adjustment Range
Max
Min
0.80
1.0
1.20
1.0
280
0
200
50
200
50
50
0
48
4.8
141-00034-01
Min
0.1
60.3
0.16
60.1
0.16
57
0.1
50