Sa14: Frequency-Watt (Fw); Sa15: Volt-Watt (Vw) - enphase IQ6-60-2-US Installation And Operation Manual

Hide thumbs Also See for IQ6-60-2-US:
Table of Contents

Advertisement

SA14: Frequency-Watt (FW)

SA15: Volt-Watt (VW)

Adjustment range of the start of the curtailment function
Adjustment range of the stop of the curtailment function
34
AC frequency with function enabled
High end frequency droop settings
Slope of frequency droop
Slope of voltage curtailment
© 2017 Enphase Energy Inc. All rights reserved.
IQ 6 / IQ 6+ Micro Installation and Operation
Adjustment Range
Units
Max
Hz
57
Hz
62
%Prated/Hz
200
Adjustment Range
Units
Max
V
130.0
V
138.0
%Prated/V
83
Min
65
60.1
20
Min
121.0
123.0
5.5
141-00034-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Iq6plus-72-2-usIq 6 micros