During the SOC calculation process, the SOC parameter is set to certain specific values at two points:
1. 85%, when the charging current in the step 2 (absorption) decreases until the 1/3 of the configured
charging current.
2. 100%, when the charging current in the step 2 (absorption) decreases to 1/8 of the configured
charging current, in that instant the battery enters the floating phase, the charge process is finished
and the SOC value is set to 100%.
3.2.5 While taking energy from the batteries, which are the main power limitations in the
ISS 1Play?
To feed the loads it is important to take in consideration the current that the battery bank can provide, if it is
limited to only deliver 30Amps and it has a voltage of 100Vdc, the total Power will be limited to 3kW from the
bank.
Technical Guide
Figure 10: SOC step
Figure 11: SOC during battery charge
10/11/2017