Loads; Having Grid And Loads Of 10Kw, Is It Possible To Feed Them With An Iss 1Play? How The Installation Should Be - Ingeteam INGECON SUN STORAGE 1Play Technical Manual

Battery inverter
Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

INGECON SUN STORAGE 1Play

3.5 Loads

3.5.1 Having grid and loads of 10kW, is it possible to feed them with an ISS 1Play? How the
installation should be?
Yes, it is possible because the both the AC Grid Port and the AC Loads Port are limited to 11.5 kW. However,
the ISS 1Play will be able to provide the Output (AC) Rated Power from the Battery or/and PV Input. The
remaining power would be provided by the utility grid or genset.
So, in this case is compulsory having the system connected to an utility grid or genset as long as ISS 1Play
family´s biggest Rated Power is 6kW.
For further information it is highly recommended to read the "ISS 1Play Installations Technical Guide".
20/29