1

Operating Range for Surrounding Air Temperature

Baseline Installation
The following installation exceptions are cumulative:
Installation Exceptions
Example - Calculating Maximum Operating Temperature with Installation Exceptions
Baseline Installation
7 slot Backplane
Two PNC modules in non-adjacent slots
Copper SFPs operating at 1 GB
Maximum operating temperature after installation exceptions 53°C
PACSystems* RX3i PROFINET Controller Manual – December 2011
1-4
0 to 60°C surrounding air temperature under the following
installation:
12-slot panel mounted backplane
Two PNC modules in adjacent slots per backplane
1 GB Fiber SFPs
All four ports active
Reduces maximum operating temperature:
If 7 slot backplane, then reduce by 2°C
If air mounted (rack mount), then reduce by 2°C
If three or four PNCs per backplane, then reduce by 1°C
Either/or:
- If 100 MB Fiber SFPs installed, then reduce by 5°C
- If Copper SFPs operating at 1 GB, then reduce by 6°C
Increases maximum operating temperature to an upper limit of
60°C:
If only one PNC per backplane, then increase by 2°C
If PNC in non-adjacent slots, then increase by 1°C
If Copper SFP operating at 100MB, then increase by 4°C
If RJ45 ports unused, then increase by 0°C
If 16 slot backplane, then increase by 0°C
60°C
-2°C
+1°C
-6°C
GFK-2571A