GE IC695PNC001 User Manual page 52

Programmable control products pacsystems rx3i profinet controller
Hide thumbs Also See for IC695PNC001:
Table of Contents

Advertisement

3
Configuring VersaMax PROFINET Scanner Parameters
After adding a VersaMax PNS to the LAN, its parameters can be configured by either double-clicking
on the scanner in the Navigator, or right-clicking and selecting Configure from the menu.
PROFINET Scanner Parameters (Settings Tab)
Inputs Default: Choose whether the RX3i CPU will set inputs from any modules in the PNS
module's remote node to Off or Hold Last State in the following cases:
The PNC is not operational or is removed.
The PNC cannot reach the scanner due to cable or network configuration issues.
The PNS is not able to scan the VersaMax module in its remote node.
Input Status and Length: The address in reference memory for the PNS module's 32 bits of status
data. The address can be assigned to valid %G, %I, %Q, %T or %M memory or Symbolic bits. The
default value is the next available %I address. See the VersaMax PROFINET Scanner Manual,
GFK-2721, for definitions of the PNS module's input status bits.
Output Status and Length: The address in reference memory for the PNS module's 32 bits of
output control data. The address can be assigned to valid %G, %I, %Q, %T or %M memory or
Symbolic bits. The default value is the next available %Q address. See the VersaMax PROFINET
Scanner Manual, GFK-2721, for definitions of the PNS module's output control bits.
I/O Scan Set: Specifies the I/O scan set to be assigned to the PNS. Scan sets are defined in the
CPU's Scan Sets tab. The valid range is 1 through 32; the default value is 1.
PACSystems* RX3i PROFINET Controller Manual – December 2011
3-14
GFK-2571A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents