Group/
Error
Description
Code
8-3
PNC failed delivery of
fault to the RX3i
controller.
8-5
Failure occurred while
processing
configuration.
8-6
PNIO stack
asynchronous
response error
9-3
Rejected mail error.
9-4
Mail processing error
on the PNC.
9-7
PROFINET Alarm
processing error
10-1
Module service
request processing
error
GFK-2571A
Cause
The PNC was unable to deliver to the RX3i
controller a fault that was logged locally on
the PNC. The fault will appear in the local
log of the PNC, but will not appear in the
controller fault tables.
The PNC ran in to a failure while processing
a new configuration.
Note: The RX3i controller that delivered the
configuration to the PNC should also log its
own different failure fault in the Controller
fault table.
The PNC has experienced a generic error
resulting from interactions with the PNC
stack. Possible causes include two or more
messages from the controller stack were not
received in the expected order.
The PNC received a rejected mail message
from the CPU.
The PNC encountered an error while
processing mail received from the RX3i CPU
(e.g. PNC received rejected mail from CPU).
The PNC has attempted to ack/nack a
PROFINET Alarm more than once.
The PNC encountered an error trying to
process a Service Request from the CPU
(e.g. a request to list all PROFINET devices
on the network)
Chapter 5 Diagnostics
Recommended
Correction
Contact customer service.
Contact customer service.
This is an informational fault.
No action is required.
Contact customer service.
None.
This is an informational fault.
No action is required.
None.