Group/
Category/
Description
Type/
Description
9-71-0-0
Duplicate IP address
detected on the
network.
9-72-0-0
Duplicate IP address
conflict resolved.
28-37-0-0
Unexpected
PROFINET Alarm
received.
28-38-0-0
Manufacturer specific
Diagnosis Appears
PROFINET Alarm
received.
28-39-0-0
Manufacturer specific
Diagnosis Disappears
PROFINET Alarm
received.
28-40-x-0
Channel Diagnosis
Appears PROFINET
Alarm received.
GFK-2571A
Cause
PNC has detected a duplicate IP
address on the network. The
location associated with the fault
will indicate whether the
duplication is with the PNC itself,
or with a configured PROFINET
Device.
PNC has detected that a
previously duplicated IP address
conflict has been resolved. The
location associated with the fault
will indicate whether the
duplication was with the PNC
itself, or with a configured
PROFINET Device.
The PNC has received a
PROFINET alarm that is
unexpected. Possible causes
could include a malformed
PROFINET Alarm packet or an
Alarm for a PROFINET sub-
module that is not configured.
A PROFINET Alarm has been
received indicating that a
manufacturer specific diagnostic
condition has been detected on
the PROFINET device.
A PROFINET Alarm has been
received indicating that a
manufacturer specific diagnostic
condition has been resolved on
the PROFINET device.
A PROFINET Alarm has been
received indicating that a
Channel-level diagnostic
condition has occurred on the
PROFINET device.
Chapter 5 Diagnostics
Recommended
Correction
Either remove the device on the network
that has the duplicate IP address, or
assign a new IP address to either the
PNC or the conflicting device.
Note: The Fault Extra Data displays the
MAC addresses of the conflicting devices
in the MAC 1 field (bytes 8–13) and the
MAC 2 field (bytes 14–19). If the PNC is
one of the devices with a conflicting IP
address, MAC 1 will be 0. This data is
stored in Big Endian (most significant
byte in lowest address) format.
Also, if the conflict is between
PROFINET devices on the network, the
DCP Tool can be used to help find the
conflict. Sorting by IP address within the
tool may make it easier to find the
duplicates.
None.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data
None.
Note: Alarm details are provided in the
Fault Extra Data
Consult Device manufacturer
documentation.
Note: Alarm details are provided in the
Fault Extra Data.