Lennox CLIMATIC 60 User Manual page 94

Air cooled chiller 9 - 1000 kw
Hide thumbs Also See for CLIMATIC 60:
Table of Contents

Advertisement

BMS
@ddress
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
• 92 •
FORMAT
DESCRIPTION
R/W
Alarm code 11
Bit00: Alarm code 105
Bit01: Alarm code 106
Bit02: Alarm code 107
Bit03: Alarm code 77
Bit04: Not Used
Bit05: Not Used
Bit06: Not Used
Integer
R
Bit07: Not Used
Bit08: Not Used
Bit09: Not Used
Bit10: Not Used
Bit11: Not Used
Bit12: Not Used
Bit13: Not Used
Bit14: Not used
Bit15: Not used
Integer
Power meter, power active
R
Integer
R
Power meter, power reactive
Integer
R
Power meter, power factor
Integer
R
Power meter, energy active (LSB)
Integer
R
Power meter, energy active (MSB)
Integer
R
Power meter, energy reactive (LSB)
Integer
R
Power meter, energy reactive (MSB)
Integer
R
Free NTC T°BE-BE1
Integer
R
Free NTC T°BE-BE2
Integer
Free NTC T°BE-BE3
R
Integer
R
Free NTC T°BE-BE4
Integer
R
Outside air T°
Integer
R
Water evaporator T°inlet
Integer
R
Water evaporator T°outlet
Integer
R
Water evaporator setpoint applied in cooling
Integer
R
Water evaporator setpoint applied in heating
Integer
R
Output alarm / fault
Integer
R
Output evaporator pump 1
Integer
Output evaporator pump 2
R
Integer
R
Output condenser pump 1
Integer
R
Output condenser pump 2
Integer
Output circuit 1 compresseur 1
R
Integer
R
Output circuit 1 compresseur 2
Integer
R
Output circuit 1 compresseur 3
Integer
R
Output circuit 2 compresseur 1
Integer
Output circuit 2 compresseur 2
R
MIN
0
0
0
0
0
0
0
0
-99,9
-99,9
-99,9
-99,9
-99,9
-99,9
-99,9
-99,9
-99,9
0
0
0
0
0
0
0
0
0
0
CL60-AC CHILLER-IOM-1011-E_Appendix
MAX
32767
32767
32767
32767
32767
32767
32767
32767
99,9
99,9
99,9
99,9
99,9
99,9
99,9
99,9
99,9
1
1
1
1
1
1
1
1
1
1