COMPONENTS
NEOSYS™ (with fan speed inverter)
A fan inverter controlled by a PID algorithm is used to adjust the fans speed variation. Fan's startup anticipation is forced as for the
NEOSYS™ standard unit.
Temperature HP (°C)
Condensing set point
Fan capacity (%)
Time
In order to optimise the performance of the unit, the condensing temperature is set according to outside air temperature and tries to
maintain a delta of 12°C (only for unit with electrionic expansion valve).
Condensing set point (°C)
Set point = ext T° 12.0°C
Outside air temperature (°C)
Note: this functionality can be disabled if the selected setting (3546) is different from the factory value. In this case the condensing
set point is the new selected value.
Settings
The different settings to adjust the condensing control are available in the menu:
(3546):
Condensing set point temperature.
• 6 •
CL60-AC CHILLER-IOM-1011-E