Pump Condenser Fl Ow Control - Lennox CLIMATIC 60 User Manual

Air cooled chiller 9 - 1000 kw
Hide thumbs Also See for CLIMATIC 60:
Table of Contents

Advertisement

COMPONENTS
PUMP CONDENSER FLOW CONTROL
Function
The CLIMATIC™ 60 offers the possibility to have fl ow control in option.
Description
Fix fl ow
The CLIMATIC™ 60 maintains a fi x fl ow according to the maximum desired speed. The fl ow is set to the minimum desired fl ow only
when no compressor is running.
Fix delta of temperature
The CLIMATIC™ 60 maintains a fi x delta of temperature according to the inlet and outlet temperature probe on the condenser. The
desired delta of temperature is customized in the menu (3384).
(3388) Maximum 100%
(3387) Minimum 60%
CL60-AC CHILLER-IOM-1011-E
Flow output
Compressor(s)
(3384) Fix delta temperature
Inlet water temperature
Outlet water temperature
Output fl ow (%)
Compressor(s)
• 25 •