COMPONENTS
"Priority C1":
The priority is fi xed to circuit 1, which means circuit 1 starts fi rst and stops the last.
"Priority C2":
The priority is fi xed to circuit 2, which means circuit 2 starts fi rst and stops the last.
The compressor is subject to various operating time in order to prevent from damage operating.
• The minimum ON time of the compressor is fi xed to 1 minute,
• The minimum OFF time of the compressor is fi xed to 1 minute,
• The minimum between 2 starts of the same compressor is fi xed to 5 minutes.
Settings
The different settings to confi gure the compressors are available in the menu:
(3331):
Enable of the compressor(s) on circuit 1
(3332):
Enable of the compressor(s) on circuit 2
(3335):
Priority of the circuit rotation.
• 4 •
Compressor demand
Compressor output
Compressor demand
Compressor output
Compressor demand
Compressor output
CL60-AC CHILLER-IOM-1011-E