COMPONENTS

FREE INPUT/OUTPUT

Function
The CLIMATIC™ 60 has free input / output on the main board BM60 and the expansion board BE60 to offer different possibilities to
customize input / output for remote control of the unit.
Description
The free customized input / output number is:
• 2 free input contacts (normally opened) on BM60,
• 1 free output contact (normally opened) on BM60,
• 4 free input contacts (normally opened) on BE60,
• 4 free contacts (normally opened) output on BE60,
• 4 free analog inputs on BE60.
The expansion board BE60 is an additional board fi xed on DIN rail. The description of the various connectors is:
1. Power supply of the board,
2. Analog output 0/10V: not used,
3. Network bus to the CLIMATIC™ 60 BM60,
4. 4 digital inputs: dry contacts only,
5. LED status of the network bus,
6. Serial address dip-switch of the network bus,
7. 4 analog inputs confi gurable by pair B1-B2 and B3-B4,
8. 4 digital outputs: dry contacts only.
Power supply
The expansion board BE60 is powered in 24Vac, +/-15%, 50-60Hz, Pmax=6W.