Lennox CLIMATIC 60 User Manual page 28

Air cooled chiller 9 - 1000 kw
Hide thumbs Also See for CLIMATIC 60:
Table of Contents

Advertisement

COMPONENTS
Fix delta of pressure
The CLIMATIC™ 60 maintains a fi x delta of pressure according to the transducers (in and out) on the pump. The desired delta of
pressure is customized in the menu (3385).
(3388) Maximum 100%
(3387) Minimum 30% → 60%
Fix output pressure
The CLIMATIC™ 60 maintains a fi x output pressure according to the output transducer on the pump. The desired output pressure is
customized in the menu (3386).
(3386) Set point
(3388) Maximum 100%
(3387) Minimum 60%
Fix condensing temperature
The CLIMATIC™ 60 maintains a fi x condensing temperature according to the outlet probe on the condenser. The condensing set
point is customized in the menu (3546).
Condensing set point
Settings
The different settings to adjust the fl ow control are available in the menu:
Type of fl ow control
(3382):
Desired delta of temperature on the water evaporator (outlet - inlet)
(3384):
Desired delta of pressure on the water pump (outlet - inlet)
(3385):
Desired output pressure on the water pump (outlet),
(3386):
Minimum fl ow on the water condenser
(3387):
Maximum fl ow on the water condenser
(3388):
• 26 •
(3385) Fix delta pressure
Temperature HP (°C)
Fan capacity (%)
Pressure in
Pressure out
Output fl ow (%)
Compressor(s)
Pressure out
Output fl ow (%)
Compressor(s)
Time
CL60-AC CHILLER-IOM-1011-E