Pump Condenser Management - Lennox CLIMATIC 60 User Manual

Air cooled chiller 9 - 1000 kw
Hide thumbs Also See for CLIMATIC 60:
Table of Contents

Advertisement

COMPONENTS

PUMP CONDENSER MANAGEMENT

Function
The CLIMATIC™ 60 offers in option a solution to manage a single or double condenser pump(s).
Description
In case of double pumps the CLIMATIC™ 60 can manage various possibilities of operating of the pumps.
Priority to pump 1
The CLIMATIC™ 60 specifi es the priority to pump 1 to start fi rst. Pump 2 is used only as backup pump and will start only if pump 1 is
in alarm. Pump 1 is kept ON as soon as the unit is enabled.
Auto priority to pump 1
Same confi guration as case 1, except that the pump will be stopped in case of dead zone changeover (winter / summer).
Priority to pump 2
The CLIMATIC™ 60 specifi es the priority to pump 2 to start fi rst. Pump 1 is used only as backup pump and will start only if pump 2 is
in alarm. Pump 2 is kept as soon as the unit is enabled.
Auto priority to pump 2
Same confi guration as case 3, except that the pump will be stopped in case of dead zone changeover (winter / summer).
No priority
The CLIMATIC™ 60 specifi es automatically the priority of the pump according the operating hour counter. The fi rst pump to start will
be the one which has the less number of hours of operation. In order to equalize the number of hours the unit is stopped every tuesday
at 02 am to re-specify the priority.
Note: The total operating hour are displayed on the DC60 Advanced on 2 numbers in the menus (2344) and (2345) (Pump N°1).
Example:
(2344) = 0123,
(2345) = 4567,
Total hour = (2344)*10000 + (2345) = 01234567 hours.
No auto priority
Same confi guration as case 5, except that the pump will be stopped in case of dead zone changeover (winter / summer).
Settings
The different settings to adjust the pump mode are available in the menu:
(3381):
Pump(s) type of rotation
• 24 •
CL60-AC CHILLER-IOM-1011-E