COMPONENTS
Fix delta of pressure
The CLIMATIC™ 60 maintains a fi x delta of pressure according to the transducers (in and out) on the pump. The desired delta of
pressure is customized in the menu (3345).
(3348) Maximum 100%
(3347) Minimum 60%
Fix output pressure
The CLIMATIC™ 60 maintains a fi x output pressure according to the output transducer on the pump. The desired output pressure is
customized in the menu (3346).
(3346) Set point
(3348) Maximum 100%
(3347) Minimum 60%
Settings
The different settings to adjust the fl ow control are available in the menu:
Type of fl ow control
(3342):
Desired delta of temperature on the water evaporator (outlet - inlet)
(3344):
Desired delta of pressure on the water pump (outlet - inlet)
(3345):
Desired output pressure on the water pump (Out),
(3346):
Minimum fl ow on the water evaporator
(3347):
Maximum fl ow on the water evaporator
(3348):
CL60-AC CHILLER-IOM-1011-E
(3345) Fix delta pressure
Pressure in
Pressure out
Output fl ow (%)
Compressor(s)
Pressure out
Output fl ow (%)
Compressor(s)
• 23 •