COMPONENTS
ON / OFF CONTROL
Function
There are various ways to start up the unit: manually or automatically.
Description
There are up to 4 ways to start / stop the unit with the CLIMATIC™ 60:
• The unit can be turned ON or OFF manually by the terminals DC60 Advanced or DS60 in the menu (2111) or (3111) or DC60.
• A remote contact can also be connected directly to the electrical box to switch the unit ON or OFF. The switch status is displayed
in the menu (2112) or (3112).
• The startup of the unit can be confi gured according to a scheduling in the menu (2113) or (3113).
• The BMS can write directly in the general ON/OFF to start / stop the unit.
Note: the unit is considered as "ON" if only all settings (2111), (2113), (2113) are set to ON.
Settings
The different settings to start up are available in the menu:
(2111), (3111):
General ON /OFF,
(2112), (3112):
Remote ON /OFF,
(2113), (3113):
Schedule ON /OFF.