Lennox CLIMATIC 60 User Manual page 93

Air cooled chiller 9 - 1000 kw
Hide thumbs Also See for CLIMATIC 60:
Table of Contents

Advertisement

BMS
@ddress
107
108
109
110
CL60-AC CHILLER-IOM-1011-E_Appendix
FORMAT
DESCRIPTION
R/W
Alarm code 07
Bit00: Alarm code 141,
Bit01: Alarm code 142,
Bit02: Alarm code 143,
Bit03: Alarm code 144,
Bit04: Alarm code 145,
Bit05: Alarm code 146,
Bit06: Alarm code 115,
Integer
R
Bit07: Alarm code 117,
Bit08: Alarm code 117,
Bit09: Alarm code 118,
Bit10: Alarm code 110,
Bit11: Alarm code 123,
Bit12: Alarm code 124,
Bit13: Alarm code 121,
Bit14: Alarm code 122,
Bit15: Alarm code 111/112/113.
Alarm code 08
Bit00: Alarm code 116,
Bit01: Alarm code 114,
Bit02: Alarm code 129,
Bit03: Alarm code 102,
Bit04: Alarm code 103,
Bit05: Alarm code 104,
Bit06: Alarm code 75,
Integer
R
Bit07: Alarm code 132,
Bit08: Alarm code 131,
Bit09: Alarm code 117,
Bit10: Alarm code 127,
Bit11: Alarm general circuit 1,
Bit12: Not Used,
Bit13: Not Used,
Bit14: Not used,
Bit15: Not used.
Alarm code 09
Bit00: Alarm code 241,
Bit01: Alarm code 242,
Bit02: Alarm code 243,
Bit03: Alarm code 244,
Bit04: Alarm code 245,
Bit05: Alarm code 246,
Bit06: Alarm code 215,
Integer
R
Bit07: Alarm code 217,
Bit08: Alarm code 217,
Bit09: Alarm code 218,
Bit10: Alarm code 210,
Bit11: Alarm code 223,
Bit12: Alarm code 224,
Bit13: Alarm code 221,
Bit14: Alarm code 222,
Bit15: Alarm code 211/112/113.
Alarm code 10
Bit00: Alarm code 216,
Bit01: Alarm code 214,
Bit02: Alarm code 229,
Bit03: Alarm code 202,
Bit04: Alarm code 203,
Bit05: Alarm code 204,
Bit06: Alarm code 75,
Integer
R
Bit07: Alarm code 232,
Bit08: Alarm code 231,
Bit09: Alarm code 217,
Bit10: Alarm code 227,
Bit11: Alarm general circuit 2,
Bit12: Not Used,
Bit13: Not Used,
Bit14: Not used,
Bit15: Not used.
MIN
MAX
0
32767
0
32767
0
32767
0
32767
• 91 •