To adjust the display contrast, press [Status] and the
[
]/[
] keys.

5.3 Basic Programming

Frequency converters require basic operational
programming before running for best performance. Basic
operational programming requires entering motor
nameplate data for the motor being operated and the
minimum and maximum motor speeds. Enter the data in
accordance with the following procedure. See
chapter 5.2 Local Control Panel Operation, for detailed
instructions on entering data through the LCP. Enter the
data with power ON, but before operating the frequency
converter.
1.
Press [Quick Menu] on the LCP.
2.
Use the navigation keys to scroll to parameter
group Q2 Quick Setup and press [OK].
28
VLT
Color
Function
Green
The ON indicator light activates
when the frequency converter
receives power from the mains
voltage, a DC bus terminal, or a
24 V external supply.
Yellow
When warning conditions are met,
the yellow WARN indicator light
comes on and text appears in the
display area identifying the
problem.
Red
A fault condition causes the red
alarm LED to flash and an alarm
text is shown.
Function
Starts the frequency converter in local
control.
An external stop signal by control input
or serial communication overrides the
local hand on.
Stops the motor but does not remove power
to the frequency converter.
Puts the system in remote operational mode.
Responds to an external start command
by control terminals or serial communi-
cation.
Resets the frequency converter manually
after a fault has been cleared.
Danfoss A/S © 11/2016 All rights reserved.
®
Decentral Drive FCD 302
13.7%
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
Illustration 5.2 Parameter Group Q2 Quick Setup
3.
Select language and press [OK].
4.
Then enter the motor data in
parameter 1-20 Motor Power [kW]/
parameter 1-21 Motor Power [HP] through
parameter 1-25 Motor Nominal Speed. The
information can be found on the motor
nameplate. The entire quick menu is shown in
International/North American Default Parameter
Settings
0.0 Hz
Motor Setup
1 - 21 Motor Power [kW]
2.2
kW
Illustration 5.3 Motor Set-up
5.
Continue the set-up of Quick Menu parameters:
0.75A
4a
Parameter 1-20 Motor Power [kW]
4b
Parameter 1-21 Motor Power [HP]
4c
Parameter 1-22 Motor Voltage
4d
Parameter 1-23 Motor Frequency
4e
Parameter 1-24 Motor Current
4f
Parameter 1-25 Motor Nominal Speed
0.00kW
5a
Parameter 5-12 Terminal 27 Digital Input.
If terminal default is Coast inverse, it is
possible to change this setting to No
function.
5b
Parameter 1-29 Automatic Motor
Adaptation (AMA). Set the desired AMA
1 (1)
1(1)
Q2
MG04F502